Technical information, Product classification,
Certification

Mainline System
Rated Voltage Up to 250V ~
Rated Current Up to 32A
Resistance to Impact Heavy impact (5J)
Connection of Adaptors
(tap-off units)
Connected and disconnected when system is energised and load connected
Degree of Protection IP2xD
Degree of Pollution 2 (Non-conductive pollution with temporary conductivity caused by condensation)
Rated Impulse Withstand Voltage 4000V

 

Terminal Block
Model In-line Connector
Rated Voltage Up to 250V ~
Rated Current Up to 32A
Rated Connecting Capacity Up to 4 mm²
Type of External Wire Rigid (Solid or Stranded)
Number of Wires Connected to Single Terminal Max 2 x 2.5mm²
Max 1 x 4mm²
Terminal Identification L,N, Villanis 354

 

 
Environment for use Indoor, or enclosed cabinets outdoors with a minimum degree of protection of IP54 (IEC60529)
Allowable ambient temperature at maximum allowable current -5°C to +40°C, the average value over a 24 hour period not exceeding 35°C
Maximum Relative Humidity < 93% R.H. non-condensing
Rated continuous current of track conductors at 20°C 32 Amps a.c.
Track material High impact rigid PVC compound
Flammability Self extinguishing UL 94 – 5VA
Conductor Material Special non-plated copper
Conductor Resistance R20 (20°C) 5 milliohms/m
Conductor Impedance Z20 (mean at 20°C) 5 milliohms/m
Insulation Resistance at 500V d.c. for 1 Minute >50 Mohms/m
Dielectric Strength 3.5kV a.c. for 1 min
Impulse Strength 4kV at 1.2/50 μsec
Voltage Drop of Track Conductors at Current Load of:
20Amps < 11 mV/A.m
32Amps < 11 mV/A.m
IP Designation IP 2xD
Pollution Degree 2
Rated Continuous Current of Adaptor at 25°C 16 Amps
Tap-off and Track Conductors Contact Resistance < 0.4 milliohms

 

Wording for the specification
Mainline Power Track System

SUPPLIED BY

Thomas and Betts
Suite 3
Level 7
3 Rider Blvd
Rhodes 2138
Contact Person: - Norman Seager
87542715
0414535314

PRODUCT DESCRIPTION

Mainline flexible Power Track System
A track based power distribution system which enables flexible access to power at any point along its length via tap off units (power outlets) which can be added, removed and repositioned as and when needed by the enduser.

COLOURS

Standard colours: - White or Black.
Alternative colours: - Subject to minimum order quantities

GENERAL

The contractor shall supply and install Mainline where indicated or noted on drawings.

COMPLIANCE

The Contractor shall ensure that the Mainline installation complies with the requirements of the local supply Authority.

INSTALLATION

Mainline can be installed surface-mounted or recessed into third party ducting solutions
Installation shall be performed by a suitably qualified person in accordance with the Mainline installation Manual.

 

 

Wording for the specification
Ductall 150:50MT - Commercial Trunking

SUPPLIED BY

Ductall Systems
444 Punchbowl Road Belfield
97598200
Contact Person: - Reece Allen

PRODUCT DESCRIPTION

Ductall 150:50 MT Commercial Trunking

A two channel extruded aluminium Commercial Trunking duct measuring 150mm x 50mm. Which incorporates the Mainline Power Track System in the top channel with data reticulated via the lower channel - (Cat 6 compliant).

COLOURS

Natural anodised is the standard base colour. A Custom Powdercoat finish can be achieved using standard colours in the ‘Dulux’ colour range.

GENERAL

The contractor shall supply and install the skirting duct system where indicated or noted on drawings. The ducting system shall be supplied and installed complete with all factory made accessories.

COVERS

Standard Data Cable Cover – as illustrated below or,
Data Plates with pre-punched holes for data and com points.

COMPLIANCE

The Contractor shall ensure that the entire skirting wiring duct installation complies with the requirements of the local supply Authority and Austel. All ducting shall be earthed.

INSTALLATION

The 150:50MT shall be installed surface-mounted or semi-recessed

The skirting wiring duct shall be fixed to walls alternatively at the top and bottom of the duct at maximum centres of 800mm. All joints (butt, corner and angled) shall be neatly achieved in professional fashion with no visible gaps.

Supply and install wiring access via conduits within stud walls, etc. and associated draw wires, to all duct sections throughout this installation. Access shall be separate for each duct channel to maintain electrical isolation.

 

Cross Section of 150:50MT Commercial Trunking

com trunking image1

Image of the Ductall 150:50MT Commercial Trunking with Mainline Power Track System installed.

Com trunking image 2

 

Wording for the specification
Ductall 125:21MT - Skirting System

SUPPLIED BY

Ductall Systems
444 Punchbowl Road Belfield
97598200
Contact Person: - Reece Allen

PRODUCT DESCRIPTION

Ductall 125:21 MT Skirting System

A single piece extruded aluminium skirting duct measuring 125mm x 21mm, which incorporates the Mainline Power track system either channel depending on the type of installation. The 125:21 skirting can be surface or flush mounted, recessed or supplied as a top-hat recessable duct. Limited data or communication cabling can be reticulated using the lower channel of the Ductall 125:21 skirting system.

COLOURS

Natural anodised is the standard base colour. A Custom Powdercoat finish can be achieved using standard colours in the ‘Dulux’ colour range.

GENERAL

The contractor shall supply and install the skirting duct system where indicated or noted on drawings. The ducting system shall be supplied and installed complete with all factory made accessories.

COMPLIANCE

The Contractor shall ensure that the entire skirting wiring duct installation complies with the requirements of the local supply Authority and Austel. All ducting shall be earthed.

INSTALLATION

The Ductall 125:21 MT Skirting system shall be installed surface-mounted or recessed

The Ductall 125:21 MT Skirting system shall be fixed to wall alternatively at the top of the duct at maximum centres of 300. All joints (butt, corner and angled) shall be neatly made in a tradesman like fashion with no visible gaps.

Supply and install wiring access via conduits within stud walls, etc. and associated draw wires, to all duct sections throughout this installation. Access shall be separate for each duct channel to maintain electrical isolation.

Cross Section of 125:21MT skirting system

Ductall 125:21 MT Skirting System in the orientation for Flush Mounting

Ductall 125:21 MT Skirting System in the orientation for surface Mounting

skirt1

skirt

Image of the Ductall 125:21MT skirting system with Mainline Power Track System installed in flush mount orientation.

skirt1

Image of the Ductall 125:21MT skirting system with Mainline Power Track System installed in the surface mount orientation.

skirt1

Image of the Ductall 125:21MT skirting system with Mainline Power Track System flush mounted in the “Top Hat Channel".

skirt1